Navien · Heat pump troubleshooting
IoT module not working or will not pair with Multikit
What is going on
LEDs show nothing, or the app will not connect.
Likely causes
- Module connector not seated
- Faulty module
Check in this order
- Check the module connector and reseat it.
- Restart Multikit and put the module in Multikit Pairing Mode (one short press, Bluetooth LED blinks blue).
- If it persists after repeated tries, replace the module.
Applies to: NAC-10SM IoT module on NAZ heat pump and NAE air conditioner
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAC-10SM IoT Module Operation & Installation Manual, Troubleshooting (Multikit), p.20. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.