Navien · Heat pump troubleshooting
IoT module: both LEDs blinking red (Multikit)
What is going on
In Multikit mode the module cannot talk to the unit. No unit data in the app. Also blinks both LEDs red for a FOTA (firmware update) error.
Likely causes
- Loose connector
- Damaged cable
Check in this order
- Turn off power at the disconnect before opening the unit.
- Reseat the module connector.
- Check the cable. Replace it if it is damaged; do not repair it.
- The error clears by itself once communication returns. FOTA errors cannot be cleared with the button.
Applies to: NAC-10SM IoT module on NAZ heat pump and NAE air conditioner
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NAC-10SM IoT Module Operation & Installation Manual, Troubleshooting (Multikit) and Error Indication, p.21. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.