Worked example: natural gas orifice at 5,000 and 8,000 ft

96V96MDV

What is going on

A worked example from the manual showing how the orifice drops as altitude rises. It uses a regional natural gas value of 900 BTU per cubic ft and 14,000 BTU per burner at sea level. The sea level orifice is #49 on the 3.5 in W.C. column. With the 4 percent per 1,000 ft de-rate, you land on #51 at 5,000 ft and #52 at 8,000 ft. The numbers are only an example, so use your own local gas value and the tables for a real job.

Likely causes

  • Install above sea level where input has to be de-rated
  • Checking the orifice size for a different altitude
  • Training on how the NFGC tables are read
  • Verifying that a furnace came with the right orifices for the site

Check in this order

  1. Sea level input per burner 14000 BTU/h. Sea level heating value: 900 BTU per cu ft
  2. Gas flow Q = 14000 / 900 = 15.56 cu ft per hour
  3. Orifice at sea level (3.5 in W.C. column of NFGC Table E.1.1(a)): #49
  4. Orifice at 5,000 ft (4 percent de-rate per 1,000 ft, NFGC Table E.1.1(d)): #51
  5. Orifice at 8,000 ft (4 percent de-rate per 1,000 ft, NFGC Table E.1.1(d)): #52
  6. These are example values only, confirm against the tables and your utility's gas value
  7. Have a licensed gas technician make the change and verify input

Applies to: Natural gas, example values only

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rheem 96V series installation instructions, p. 80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.