Worked example: natural gas orifice at 5,000 and 8,000 ft
What is going on
A worked example from the manual showing how the orifice drops as altitude rises. It uses a regional natural gas value of 900 BTU per cubic ft and 14,000 BTU per burner at sea level. The sea level orifice is #49 on the 3.5 in W.C. column. With the 4 percent per 1,000 ft de-rate, you land on #51 at 5,000 ft and #52 at 8,000 ft. The numbers are only an example, so use your own local gas value and the tables for a real job.
Likely causes
- Install above sea level where input has to be de-rated
- Checking the orifice size for a different altitude
- Training on how the NFGC tables are read
- Verifying that a furnace came with the right orifices for the site
Check in this order
- Sea level input per burner 14000 BTU/h. Sea level heating value: 900 BTU per cu ft
- Gas flow Q = 14000 / 900 = 15.56 cu ft per hour
- Orifice at sea level (3.5 in W.C. column of NFGC Table E.1.1(a)): #49
- Orifice at 5,000 ft (4 percent de-rate per 1,000 ft, NFGC Table E.1.1(d)): #51
- Orifice at 8,000 ft (4 percent de-rate per 1,000 ft, NFGC Table E.1.1(d)): #52
- These are example values only, confirm against the tables and your utility's gas value
- Have a licensed gas technician make the change and verify input
Applies to: Natural gas, example values only
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rheem 96V series installation instructions, p. 80. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.