Rheem · Furnace troubleshooting
Blower does not start after burners light
What is going on
The burners light and run but the blower doesn't come on, or it comes on late. On this furnace the blower should start on heat speed about 20 seconds after the burners light. With no airflow the heat exchanger gets hot fast and the furnace will trip on limit, so don't let it keep cycling like that.
Likely causes
- No voltage from the IFC HEAT terminal
- Bad capacitor or motor
- Wiring
Check in this order
- Give it the full 20 seconds before you decide anything.
- Check line voltage between HEAT and NEUTRAL on the IFC.
- Check wiring IFC to blower motor, including the plug connections.
- Check blower capacitor.
- Check blower motor.
- If the furnace is tripping the limit, fix the airflow problem before running it again.
Applies to: Rheem/Ruud (-)95P series 95% single-stage condensing gas furnace (R95PA)
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rheem R95P Installation Instructions (ManualsLib 989115), Figure 49 IFC Troubleshooting Guide, p.96 (PDF p.100). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.