Rheem · Furnace troubleshooting
Blower does not start after burners light
What is going on
R95P: blower should start on heat speed about 20 seconds after burners light.
Likely causes
- No voltage from IFC HEAT terminal
- Bad capacitor or motor
- Wiring
Check in this order
- Check line voltage between HEAT and NEUTRAL on the IFC.
- Check wiring IFC to blower motor.
- Check blower capacitor.
- Check blower motor.
Applies to: Rheem/Ruud (-)95P series 95% single-stage condensing gas furnace (R95PA)
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rheem R95P Installation Instructions (ManualsLib 989115), Figure 49 IFC Troubleshooting Guide, p.96 (PDF p.100). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.