Cement PVC vent joints

96V96MDV

What is going on

Method for joining PVC vent pipe and fittings with cleaner-primer and medium-body solvent cement.

Check in this order

  1. Cut the pipe end square, chamfer the edge, and remove all burrs and ragged edges.
  2. Clean the fitting socket and pipe joint of dirt, grease and moisture.
  3. Check the pipe fit in the socket.
  4. Wipe socket and pipe with cleaner-primer and apply a liberal coat inside the socket and outside the pipe.
  5. Apply a thin coat of cement inside the socket.
  6. Quickly apply a heavy coat of cement to the pipe end.
  7. Insert the pipe with a slight twist until it bottoms out.
  8. Hold the pipe in place for 30 seconds.
  9. Wipe away excess cement and allow 15 minutes before handling. Cure time varies with fit, temperature and humidity.

Applies to: PVC vent joints

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: 96V series installation instructions, p. 47. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.