Wall vent clearances and shielding

AUH1BUH1DH1

What is going on

Clearances depend on wall construction and vent material. Combustible walls need an air space and a shield, and wall-vent flue gas can damage nearby materials.

Check in this order

  1. Use 0 in clearance to combustible walls for PVC vent pipe.
  2. Use 1 in clearance to combustible walls for Type 29-4C stainless vent pipe.
  3. Hold a 1 in air space at combustible walls where the wall pipe passes through, and set the approved termination in place.
  4. Seal noncombustible wall penetrations with cement mortar inside and outside, with the hole sized to keep pitch and seal properly.
  5. Where flue gas could damage the wall, install a corrosion-resistant shield, at least 24 gauge stainless or aluminized, minimum 12 in x 12 in, fastened to both the inside and outside of the wall.
  6. Silicone-caulk all cracks, seams and joints within 3 ft of the vent terminal.

Applies to: Horizontal wall venting

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane installer's guide, p. 25. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.