Trane · Furnace troubleshooting

Airflow adjustment check

AUH1B

What is going on

Before changing airflow on an AUH1B furnace, check the air temperatures across the heat exchanger first. Airflow is changed at the blower motor speed taps, not in the control panel. Disconnect power before opening the blower door for any work. The blower door switch cuts power to the blower and gas valve when the door is removed, so keep all panels closed while you are measuring and do not defeat that switch.

Likely causes

  • Temperature rise outside the nameplate range
  • Blower speed set wrong for the duct system
  • Dirty filter or restricted ducts making it look like a blower speed issue
  • Panels open or door switch not engaging

Check in this order

  1. Measure inlet and outlet air temperatures with the furnace running steady, with panels closed.
  2. Confirm both are within the ranges printed on the rating nameplate.
  3. Before changing speed, check the filter and registers, because restriction is the usual cause.
  4. If airflow must change, use the wiring diagram to find the blower motor speed change.
  5. Disconnect power before opening the blower door for any work.
  6. Keep all panels closed during operation; the blower door switch cuts power to the blower and gas valve when the door is removed.
  7. Recheck temperature rise after any change.

Applies to: AUH1B furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane installer's manual (AUH1B040A9241A), p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.