Trane · Furnace troubleshooting

Airflow and temperature rise check

UH1 / DH1

What is going on

At startup on this Trane, confirm airflow by checking inlet and outlet air temperatures against the furnace rating plate. Do it with the furnace stabilized and the panels in place, because open panels give false readings. Never change a motor speed without first disconnecting power.

Likely causes

  • Temperature rise outside the nameplate range because of blower speed
  • Dirty filter or restricted ductwork reducing airflow
  • Readings taken before the furnace stabilized

Check in this order

  1. Run the furnace until temperatures stabilize with all panels closed.
  2. Check inlet and outlet air temperatures against the ranges on the furnace rating nameplate.
  3. If airflow must change, turn off power and use the wiring diagram to change the blower motor speed.
  4. Recheck the temperature rise after the change.
  5. Check the filter and registers if the rise stays out of range.

Applies to: Airflow adjustment at startup

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane 18-CD29D1-11 installer's guide, p. 36. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.