Trane · Furnace troubleshooting
Vent and inlet terminal spacing
What is going on
Terminal spacing for the vent and inlet is given in the venting figures. The numbers for each dimension depend on which termination you are building, and the reference point for each one should be confirmed against the manual drawing before you cut pipe. What I usually find going wrong is people mixing dimensions from different termination styles. Pipe supports and insulation also matter here, since a sagging or frozen pipe will cause a pressure switch trip the first time it gets cold.
Likely causes
- Exhaust and inlet ends too close, recirculating flue gas into the intake
- Dimensions mixed up between different termination styles
- Pipe unsupported, sagging and collecting condensate
- Fitting in an unheated space left uninsulated and freezing up
Check in this order
- Keep at least 9 in between the end of the exhaust pipe and the end of the inlet pipe.
- Check the 6 in minimum and 24 in maximum dimension (and the 12 in minimum and 15 in maximum dimension) against the drawing for the specific termination.
- Support vent and inlet pipe at no more than 3 ft intervals.
- Insulate any fitting that passes through an unheated space.
- Look at the terminals after install to confirm nothing blocks them.
- Run a heating cycle and confirm the pressure switch stays closed.
Applies to: Two-pipe (direct) venting
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Trane installer's guide, p. 24, 26. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.