Allied · Furnace troubleshooting

Upflow 5-ton units with 1800 cfm or more airflow

A95/A93/95G1/92G1UH

What is going on

Upflow 20C and 20D (5 ton) units that need 1800 cfm or more have to be set up with one of the listed return air arrangements. Too little return opening means high velocity, noise and a poor temperature rise.

Likely causes

  • Single undersized return for a 5 ton airflow
  • Filter or transition too small for the cfm needed
  • Return arrangement not on the approved list for 1800 cfm or more

Check in this order

  1. Use single side return with a transition sized for a 20 x 25 x 1 in. cleanable filter.
  2. Or use single side return with the optional RAB Return Air Base.
  3. Or use bottom return air.
  4. Or use return air from both sides.
  5. Or use bottom and one side return air.
  6. Check the blower performance tables for the airflow limits before you commit to an arrangement.

Applies to: 20C and 20D (5 ton) size units, upflow installations

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Allied 92G1UH installation manual, p. 6. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.