Allied · Furnace troubleshooting

Change blower speed tap

A95/A93/95G1/92G1UH

What is going on

Change the blower speed tap on the integrated control to match the heating or cooling speed needed.

Likely causes

  • Temperature rise outside the range on the rating plate
  • Cooling airflow too low or too high
  • Duct changes after install
  • Noisy or drafty registers from too much speed

Check in this order

  1. Turn off electrical power to the furnace, because the control board has line voltage nearby.
  2. Remove the blower access panel.
  3. Disconnect the existing speed tap from the control board speed terminal.
  4. Insulate any unused motor leads so they cannot touch metal.
  5. Place the unused speed tap on the integrated control PARK terminal or insulate it.
  6. Select the speed from the blower speed chart on the unit wiring diagram.
  7. Connect the selected speed tap to the control board speed terminal.
  8. Reinstall the blower access panel.
  9. Turn on power and recheck the temperature rise against the rating plate.

Applies to: Blower speed selection

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Allied 92G1UH installation instructions manual, p. 46. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.