Allied · Furnace troubleshooting
Annual service checklist
What is going on
What I usually find on a furnace that has not been looked at in a few years is a dirty blower wheel, a plugged filter and a slightly loose connection somewhere. This is the checklist for the start of each heating season, and most of it is quick. The blower motors are prelubricated, so do not oil them. Filters live outside the unit and are field supplied, so they are yours to watch monthly.
Likely causes
- Dirty blower wheel cutting airflow
- Plugged filter causing high temperature rise and limit trips
- Vent pipes blocked by snow, ice or frozen fog
- Loose wiring connections causing intermittent faults
- Supply voltage out of range or high blower amp draw
Check in this order
- Check the blower wheel for debris and clean it if needed. Blower motors are prelubricated and need no oil.
- Inspect filters monthly and clean or replace them as needed. Filters are field supplied and mounted outside the unit.
- Check exhaust and air intake pipes and connections for tightness and blockage.
- After heavy snow, ice or frozen fog, clear snow or ice from the plastic intake and exhaust pipes.
- Check all wiring for loose connections with power off.
- Check furnace supply voltage (120 VAC ±10%) and blower amp draw with a meter.
- Turn the power back on, run a full cycle and listen for anything unusual.
Applies to: Seasonal furnace service
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Allied 92G1UH installation instructions manual, p. 51. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.