Allied · Furnace troubleshooting
Burner assembly cleaning
What is going on
Clean the burners and inspect the crossovers for blockage.
Check in this order
- Turn off gas and electrical power and remove the heating compartment access panel.
- Disconnect the gas supply line and gas valve wires, labelling each wire.
- Disconnect the ignitor plug, rollout switch wires, flame sensor wire and burner ground wire, labelling each.
- Remove the four screws holding the burner/manifold assembly to the vestibule. Keep the ignitor plate from dislodging from the assembly.
- Gently clean the burner faces with a soft brush on a vacuum cleaner.
- Inspect the inside of the burners and crossovers and remove any blockage from foreign matter.
- Reinstall the burner assembly with the four existing screws. The burners self-align to the clam shells.
- Reconnect ground, flame sensor, rollout switch, ignitor, gas valve and gas supply wires.
- Check gas and electrical connections, restore power and gas, then run the furnace for 5 minutes to confirm the burners are clean and working.
- Replace the heating compartment access panel.
Applies to: 92G1UH furnace
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Allied 92G1UH installation instructions manual, p. 56. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.