Rheem · Furnace troubleshooting
Thermostat does not hold room temperature
What is going on
Rheem/Ruud (-)95P series furnace runs, but the room never gets near the setpoint. Check the thermostat's surroundings before the furnace itself.
Likely causes
- Thermostat location, affected by outside heat or air movement
- Heat anticipator setting off
- Furnace undersized for the building
Check in this order
- Check the thermostat is not affected by registers, fans, sunlight or heat in the walls, because it will read wrong and quit early or late
- Check the heat anticipator setting; an isolation relay may be needed
- Verify correct furnace sizing against the heat loss, and compare temperature rise to the rating plate to prove it is really putting out its rated heat
Applies to: Rheem/Ruud (-)95P series 95% single-stage condensing gas furnace (R95PA)
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rheem R95P Installation Instructions (ManualsLib 989115), Figure 49 IFC Troubleshooting Guide, p.96 (PDF p.100). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.