Trane · Furnace troubleshooting

Roof venting

AUH1BUH1DH1

What is going on

Roof vent. Keep a set height over snow. Seal the roof penetration. Leaks here mean wet ceilings. Too tall and the pipe gets exposed to wind and frost. Too short and snow buries it. Canada needs more snow clearance than the US.

Likely causes

  • Vent too low, buried by snow
  • Vent too tall above the roof, unsupported in wind
  • Unsealed roof penetration leaking
  • Combustion air inlet not meeting the dimensions in the figure
  • Rain cap ribs left in place restricting flow

Check in this order

  1. Keep at least 12 in clearance above the highest expected snow level (18 in in Canada).
  2. Keep the vent no more than 24 in above the roof.
  3. Seal a 2 in PVC vent through the roof using a 2 in electrical conduit flashing. Lubricate the flexible seal before pushing the pipe through.
  4. Use a roof flashing boot (field supplied) and a support (field supplied) as needed.
  5. Use the combustion air inlet with the roof vent, meeting the dimensions in the venting figure.
  6. Remove the ribs from the cap where a rain cap is used.
  7. Check for leaks in the attic after the first heavy rain.

Applies to: Vertical roof venting

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane installer's guide, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.