Allied · Furnace troubleshooting

Return air connection and sealing

A95 / A93 / 95G1 / 92G1UH

What is going on

Improper return connections can allow combustion products into the living space.

Likely causes

  • Return ducts connected to the back of the furnace
  • Gaps or leaks in the base or platform
  • Return air shared with a fireplace or stove

Check in this order

  1. Do not connect return air ducts to the back of the furnace.
  2. Seal the return air system to the furnace with sheet metal screws and joint tape.
  3. Seal the furnace airtight to the return plenum in platform installs.
  4. Do not use a door as part of the return air duct system.
  5. Make sure the base gives stable support with no sagging, cracks or gaps.
  6. Do not connect return or supply ducts to other heating devices such as a fireplace or stove.
  7. For side return, cut only within the cabinet markings and keep the opening within the stated dimensions.

Applies to: Upflow and horizontal installations with return air

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Allied 92G1UH installation instructions manual, p. 10, 14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.