Trane · Furnace troubleshooting
Reading and clearing fault history - Trane S-Series IFC
What is going on
How to pull up stored faults, wipe them and reset the furnace control to factory values with the Menu and Option buttons.
Likely causes
- Intermittent faults that are no longer active
- Settings changed by others
Check in this order
- Warning: Touch only the Menu and Option buttons on a powered board.
- Active faults scroll with Menu to 'err'. Stored faults: scroll to 'L6F' and press Option to step through the last 6.
- To erase history inside L6F hold Option 5 seconds or more; three dashes flashing 3 times confirm it is cleared.
- Factory defaults with the display at idle, press Menu and Option together for 15 seconds; 'FD' flashing 3 times confirms.
- While running, the display alternates mode and airflow every 2 seconds; an E-code flashes in between if a fault is active.
Applies to: Trane S8V2 (80%, 2-stage, variable speed, Link) and S8B1 / S8X1 / S8X2 (80%, 1- and 2-stage)
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Trane FNR-SVX003A-EN and 18-CE14D1-1A-EN - section Fault Code Recovery. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.