Allied · Furnace troubleshooting

Protecting walls from acidic flue gas

A95/A93/95G1/92G1UH

What is going on

Flue gas from a condensing furnace can be slightly acidic and can stain or eat into some building materials at the termination. A protective shield is required when the optional tee is used. Check what the exhaust will actually hit before you finish the termination.

Likely causes

  • Flue gas plume hitting siding, brick or other building material
  • Optional tee used without a shield
  • Gaps and cracks at the wall around the termination letting moisture in

Check in this order

  1. If flue gas will hit building material at the termination, install a corrosion-resistant shield at least 24 in. square.
  2. Build the shield from wood, plastic, sheet metal or other suitable material.
  3. Seal all seams, joints and cracks in the affected area with an appropriate sealant.
  4. Re-inspect the wall after the first season for staining or damage.

Applies to: Sidewall terminations

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Allied 92G1UH installation instructions manual, p. 30. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.