Rheem · Furnace troubleshooting
Measuring and adjusting manifold gas pressure
What is going on
Manifold pressure is the pressure at the gas valve outlet that actually feeds the burners. I check it with a heat call active, and I set it on high fire first. If the flame looks wrong or the furnace is over or under fired, this is where you look right after you have confirmed supply pressure is good. Take it slow when you turn the regulator screw, because small turns move the number a lot. Gas work is for the licensed tech.
Likely causes
- Flame is lazy, yellow or lifting from the burners
- Furnace is over or under fired after a conversion or altitude change
- Regulator out of adjustment
- Supply pressure not within limits
Check in this order
- Shut off gas at the manual gas valve and remove the outlet pressure tap plug
- Loosen (do not remove) the outlet tap screw with a 3/32 allen wrench
- Connect the manometer with 5/16 in. I.D. hose
- Turn gas on and apply a heat call
- Set manifold pressure to 3.5 in. w.c. (natural gas) or 10.0 in. w.c. (LP) on high fire
- Remove the regulator cap and turn the adjustment screw to set the pressure
- Replace the regulator cap securely
- Shut off gas, remove manometer and hose, and tighten the inlet tap screw
- Turn gas on, apply a heat call and check for leaks with an approved detector
Applies to: Gas valve outlet pressure
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: 96V series installation instructions, p. 75. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.