Trane · Furnace troubleshooting
Measure manifold pressure from the burner box
What is going on
Manifold pressure on this Trane has to be referenced to the burner box, not read against room air at the valve outlet. Gas work, so a licensed technician should set it. Get the reference right or the reading means nothing, and a bad reading leads to overfiring or sooting.
Likely causes
- Manifold pressure read without the burner box reference
- Tap plug not sealed after adjusting, leaving a gas leak
- Tee or tubing connection leaking at the reference line
Check in this order
- Install a field-supplied tee in the tubing between the burner box tube and the gas valve.
- Keep the regular gas valve outlet pressure tap in use as well.
- Check manifold pressure at the burner box reference.
- After adjusting, replace the manifold pressure tap threaded plug.
- Leak check the plug and tubing connections with leak detector solution.
Applies to: Manifold pressure checks
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Trane 18-CD29D1-11 installer's guide, p. 33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.