LP gas at high altitude: select orifice from drill size table
What is going on
Propane has a consistent heating value, so picking an orifice at altitude is more of a table lookup than a calculation. The catch, which people trip on, is that this furnace uses 10 in W.C. at the orifice, not the 11 in W.C. used in the NFGC LP chart. So do not use the NFGC LP orifice sizes. You reduce sea level input by 4 percent per 1,000 ft, then pick the orifice from the LP drill size table. The table applies to 90 Plus models only.
Likely causes
- LP furnace going in at high elevation
- Orifice table confusion between the NFGC chart and the furnace's own table
- Ordering orifices for a conversion kit
- After a move or a change in installation altitude
Check in this order
- Find the altitude band for the installation
- Read the reduced input per burner for that band from the LP orifice drill size table
- Select the drill size listed for that band
- Order the orifice using the part number format 62-22175-(drill size). Example: #60 drill is 62-22175-60; 1.10 mm is 62-22175-90
- Drill sizes available are 39 through 64, plus metric 1.10 mm (-90)
- Do not use the NFGC LP orifice sizes, they assume 11 in W.C.
- After fitting, verify manifold pressure and flame
Applies to: 90 Plus LP gas models at altitude
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rheem 96V series installation instructions, p. 82. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.