Trane · Furnace troubleshooting

Limit switch check during startup

UH1 / DH1

What is going on

The high limit has to open and shut the burners off at the rated outlet temperature. This is an installer's check at startup, and I always do it, because a limit that does not trip is the difference between a nuisance call and a fire. What I usually find on a bad one is that it simply never opens, and the furnace keeps firing while the plenum gets hot. Stay with the furnace the whole test and be ready to shut it down by hand.

Likely causes

  • Faulty limit switch if burners keep running and overheating is evident
  • Limit sensor not seeing heat because of mounting or position
  • Blower or airflow problem causing the limit to trip early instead
  • Wiring fault in the limit circuit

Check in this order

  1. Set the thermostat above the setpoint to bring on the gas valve.
  2. Restrict airflow by blocking the return air. Disconnecting the indoor blower can trip the inducer limit.
  3. Watch for the burners to shut off when outlet temperature reaches the rating plate maximum.
  4. If the burners do not shut off and overheating occurs, shut the furnace off manually at once and replace the limit switch.
  5. Check continuity across the limit with a meter once it cools to confirm it recloses.
  6. Remove the paper or cardboard from the return air inlet after the test.
  7. Never leave a limit bypassed or a faulty limit in service.

Applies to: All furnaces at initial startup

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane 18-CD29D1-11 installer's guide, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.