Rheem · Furnace troubleshooting
Inducer runs 60 seconds then off for 5 minutes
What is going on
R95P: pressure switch not proving.
Likely causes
- Blocked vent/intake
- Water in hoses
- Wind
- Bad pressure switch
Check in this order
- Check pressure switch, hoses and wires.
- Check for blocked vent, excess vent length/elbows, blocked heat exchanger.
- Check switches/hoses for water.
- Check inducer is wired correctly.
- Look for wind opening the switch or intermittent switch operation.
Applies to: Rheem/Ruud (-)95P series 95% single-stage condensing gas furnace (R95PA)
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rheem R95P Installation Instructions (ManualsLib 989115), Figure 49 IFC Troubleshooting Guide, p.96 (PDF p.100). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.