Rheem · Furnace troubleshooting

Inducer runs 60 seconds then off for 5 minutes

What is going on

R95P: pressure switch not proving.

Likely causes

  • Blocked vent/intake
  • Water in hoses
  • Wind
  • Bad pressure switch

Check in this order

  1. Check pressure switch, hoses and wires.
  2. Check for blocked vent, excess vent length/elbows, blocked heat exchanger.
  3. Check switches/hoses for water.
  4. Check inducer is wired correctly.
  5. Look for wind opening the switch or intermittent switch operation.

Applies to: Rheem/Ruud (-)95P series 95% single-stage condensing gas furnace (R95PA)

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rheem R95P Installation Instructions (ManualsLib 989115), Figure 49 IFC Troubleshooting Guide, p.96 (PDF p.100). Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.