Rheem · Furnace troubleshooting
Inducer runs 60 s then shuts off for 5 minutes, or runs continuously
What is going on
Rheem 90 Plus condensing furnace. Inducer runs 60 s, shuts off for 5 minutes, or never stops, and the furnace never lights. Classic proving problem. Something is keeping the pressure switch from holding.
Likely causes
- Open limit or limit circuit
- Intermittent pressure switch
- Vent restriction, excessive vent length or too small a vent
- Blocked heat exchanger
Check in this order
- Check the STATUS LED blink code first.
- Check for an open limit or limit circuit.
- Check for intermittent pressure switch operation; look at the hoses and tubing for water or kinks.
- Check the vent for restrictions, and confirm vent length and diameter are within limits.
- Check for a blocked heat exchanger. Combustion and venting work is for a licensed technician.
Applies to: Rheem (-)GRC/(-)GTC and 90RJ/90TJ 90 Plus condensing gas furnaces
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rheem (-)GRC/(-)GTC Installation Instructions 92-24161-88-00, Figure 56 IFC Troubleshooting Guide, p.54 (printed); Rheem 90RJ/90TJ Installation Instructions 92-24161-32-08, Figure 53, p.54. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.