Rheem · Furnace troubleshooting

Inducer runs 60 s then shuts off for 5 minutes, or runs continuously

What is going on

Inducer cycles on 60 s / off 5 min, or never stops, without the furnace lighting.

Likely causes

  • Open limit or limit circuit
  • Intermittent pressure switch
  • Vent restriction, excessive vent length or too-small vent
  • Blocked heat exchanger

Check in this order

  1. Check the STATUS LED blink code first.
  2. Check for an open limit or limit circuit.
  3. Check for intermittent pressure switch operation.
  4. Check the vent for restrictions and confirm vent length and diameter are within limits.
  5. Check for a blocked heat exchanger.

Applies to: Rheem (-)GRC/(-)GTC and 90RJ/90TJ 90 Plus condensing gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rheem (-)GRC/(-)GTC Installation Instructions 92-24161-88-00, Figure 56 IFC Troubleshooting Guide, p.54 (printed); Rheem 90RJ/90TJ Installation Instructions 92-24161-32-08, Figure 53, p.54. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.