Rheem · Furnace troubleshooting
Inducer (draft motor) does not start on heat call
What is going on
On the Rheem/Ruud (-)95P series 95% single-stage condensing furnace (R95PA), there is a call for heat but the inducer never starts. Take it slowly. A dead inducer can be a missing 24 V call, an open safety circuit or just a failed motor or capacitor, and you should know which before replacing anything. Line voltage is present at the inducer, so use care and a qualified tech where needed.
Likely causes
- No 24 V on W at the control
- Limit circuit open
- Inducer motor or capacitor failed
- Wiring fault between the IFC and the inducer
Check in this order
- Set the fan to AUTO and call for heat with the setpoint more than 10 F above room temperature.
- Check for 24 V on W at the IFC. If none, check thermostat mode, battery and wires.
- Check for an open limit or limit circuit; do not jumper any safety to see if the inducer starts.
- Check line voltage at the inducer and on the IFC inducer pins, with power handled safely.
- Check wires and connections from the IFC to the inducer, and the inducer capacitor (90+).
- Check the IFC last. Most failures are not the IFC.
Applies to: Rheem/Ruud (-)95P series 95% single-stage condensing gas furnace (R95PA)
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rheem R95P Installation Instructions (ManualsLib 989115), Figure 49 IFC Troubleshooting Guide, p.96 (PDF p.100). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.