Rheem · Furnace troubleshooting
Inducer does not run / does not run on low speed
What is going on
RGPE/RGLE 2-stage.
Likely causes
- No line voltage to inducer
- Capacitor
- Inducer low speed winding
Check in this order
- Check line voltage at the inducer.
- Check wires/connections IFC J2 to inducer; check line voltage between J2 pin 1 and pin 4 (high output).
- Check for 115 VAC on P2.
- Check inducer capacitor.
- Check inducer low speed; replace if needed.
Applies to: Rheem/Ruud (-)GPE upflow/horizontal and (-)GLE downflow 2-stage 80+ communicating gas furnaces
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rheem RGPE/RGLE Installation Instructions 92-24161-77-02 (ManualsLib 1287511), Figure 45 Troubleshooting Chart, p.63 (PDF p.67). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.