Inducer does not run / does not run on low speed

What is going on

On the Rheem/Ruud (-)GPE upflow/horizontal and (-)GLE downflow 2-stage 80+ communicating gas furnaces (RGPE/RGLE), the inducer will not run, or will not run on low speed. Confirm power is off before you take covers off, since the inducer circuits carry 115 VAC. Work out whether the motor is being fed power at all before condemning it.

Likely causes

  • No line voltage reaching the inducer
  • Inducer capacitor failed
  • Inducer low speed winding failed

Check in this order

  1. Check line voltage at the inducer, taking care with live meter leads.
  2. Check wires and connections from IFC J2 to the inducer, and check line voltage between J2 pin 1 and pin 4 (high output).
  3. Check for 115 VAC on P2.
  4. Check the inducer capacitor.
  5. Check the inducer low speed; replace the inducer if needed.

Applies to: Rheem/Ruud (-)GPE upflow/horizontal and (-)GLE downflow 2-stage 80+ communicating gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rheem RGPE/RGLE Installation Instructions 92-24161-77-02 (ManualsLib 1287511), Figure 45 Troubleshooting Chart, p.63 (PDF p.67). Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.