Rheem · Furnace troubleshooting

Indoor blower does not start after burners light

What is going on

On these Rheem 90 Plus condensing furnaces the burners light normally, but about 20 seconds later the main blower doesn't come on at heat speed. The furnace then usually heats up until a limit trips. That means one of three things. The integrated furnace control (IFC) isn't sending line voltage to the HEAT terminal, the wiring or motor capacitor between the board and the blower is bad, or a safety opened during the start. Line voltage is dangerous here, so be careful. Disconnect power before servicing, and this work is for a trained service technician.

Likely causes

  • No line voltage on the HEAT terminal of the IFC
  • Wiring or connector fault from the IFC to the blower motor
  • Bad blower capacitor or motor
  • Pressure switch or limit opened during the trial

Check in this order

  1. Warning: hazardous line voltage, disconnect power before servicing, work must be done by a trained, qualified service technician
  2. With the burners lit, check line voltage between HEAT and NEUTRAL on the IFC, no voltage means the control is not calling the blower
  3. With power off, check wires, connections and continuity between the IFC and the indoor blower motor
  4. Check the blower capacitor, then the motor, a weak capacitor makes a motor hum or turn slowly
  5. If a pressure switch opened during the ignition trial, follow the 2-blink steps
  6. If a limit opened, follow the 3-blink steps
  7. Read the fault history on the control before you start and again after, to see what it is tripping on

Applies to: Rheem (-)GRC/(-)GTC and 90RJ/90TJ 90 Plus condensing gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rheem (-)GRC/(-)GTC Installation Instructions 92-24161-88-00, Figure 56 IFC Troubleshooting Guide, p.54 (printed); Rheem 90RJ/90TJ Installation Instructions 92-24161-32-08, Figure 53, p.54. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.