Indoor blower does not start after burners light
What is going on
Burners light but the main blower does not start on heat speed about 20 s later.
Likely causes
- No line voltage on HEAT terminal
- Wiring from IFC to blower motor
- Bad blower capacitor or motor
- Pressure switch or limit opened during the trial
Check in this order
- Warning: Hazardous line voltage - disconnect power before servicing; work must be done by a trained, qualified service technician.
- Check line voltage between HEAT and NEUTRAL on the IFC.
- Check wires, connections and continuity between the IFC and the indoor blower motor.
- Check the blower capacitor, then the motor.
- If a pressure switch opened during the ignition trial, follow the 2-blink steps; if a limit opened, follow the 3-blink steps.
Applies to: Rheem (-)GRC/(-)GTC and 90RJ/90TJ 90 Plus condensing gas furnaces
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rheem (-)GRC/(-)GTC Installation Instructions 92-24161-88-00, Figure 56 IFC Troubleshooting Guide, p.54 (printed); Rheem 90RJ/90TJ Installation Instructions 92-24161-32-08, Figure 53, p.54. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.