Horizontal vent termination through wall

UH1 / DH1

What is going on

On a horizontal wall termination, the thing I find wrong most often is a vent set too close to grade. Snow drifts, mulch or a flower bed will bury it and the furnace trips on the pressure switch in the first cold snap. Vent and inlet terminals must clear the expected snow level, and the dimensions in the figures are what the manufacturer tested, so use them.

Likely causes

  • Terminals too low and covered by snow or landscaping
  • Exhaust and inlet too close, recirculating flue gas
  • Insufficient overhang
  • Elbow and tee spaced too far apart, upsetting the termination dimensions
  • Wrong termination kit mixed with the figure dimensions

Check in this order

  1. Locate the vent and inlet terminals at least 12 in above the normally expected snow level.
  2. Maintain at least 12 in above the highest anticipated snow level or grade, whichever is higher.
  3. Use at least 12 in of overhang for the termination (per figure).
  4. Keep the exhaust and inlet ends separated by at least 9 in measured end to end (per figure).
  5. Keep the elbow and tee as close together as possible.
  6. Use 6 in minimum to 24 in maximum between the terminal and the adjacent fitting (per figure).
  7. Termination kits BAYVENT200B or BAYAIR30AVENTA can replace the terminal options shown in the figures.
  8. Walk around outside after install and check for obstructions.

Applies to: Horizontal venting through wall

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane AUH1B080A9421B installer's manual, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.