Trane · Furnace troubleshooting

Horizontal installation support and drain

UH1/DH1

What is going on

When you lay a furnace on its side, the coil and the furnace both need real support and a way to get rid of water. People forget the coil drain, and the first summer there is a ceiling stain. The rules below are for the UH1 upflow converted to horizontal and the DH1 downflow in horizontal. Take your time on support, because a sagging cabinet can bind the doors and put stress on the drain connections.

Likely causes

  • Upflow UH1 being converted to a horizontal install
  • DH1 downflow furnace set in the horizontal position
  • A horizontal evaporator coil or 95% furnace sitting over a finished space
  • New install where the cased coil needs stabilizing

Check in this order

  1. Install an auxiliary drain pan under a horizontal evaporator coil or 95% furnace. Run the auxiliary drain to a separate line (no trap needed)
  2. Fit the three brackets included with downflow furnaces to stabilise the furnace and TXC cased coil, using the rear coil case screws and four bracket screws
  3. Place the 2/4TXC coil downstream of the furnace. The coil apex may point toward or away from the furnace
  4. Support the furnace at both ends and in the middle
  5. Raise the furnace at least 6 in so the condensate drain can exit the cabinet
  6. Check that the unit has the slope required by the installer's guide so condensate runs the right way

Applies to: UH1 upflow converted to horizontal and DH1 downflow in horizontal position

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane installer's guide 18-CD29D1-11, p. 7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.