Rheem · Furnace troubleshooting

Heat call troubleshooting walk-through (two-stage communicating IFC)

R96V/96MDV

What is going on

Order of checks from the factory diagnostic chart when a heat call does not end in high-fire heat.

Likely causes

  • No W1/W2 or communicated call
  • Dipswitch or test-mode setting
  • Inducer not starting or pressure switches not closing
  • No spark or no flame proof
  • Blower not starting on heat speed

Check in this order

  1. Communicating systems pull E1/E2 off the thermostat and jumper W1-R and W2-R to force high heat. Legacy: confirm 24 VAC on W1 and W2 at the IFC.
  2. Displays should light and show a steady H (h = low heat only). Flashing H means check the dipswitches.
  3. Inducer should pre-purge about 30 seconds at high speed. If it runs 60 seconds then stops for five minutes with 45, 46 or 57 showing, work the pressure switch fault.
  4. Watch for spark; the gas valve is powered about 7 seconds per trial, four trials before a one-hour lockout. 11 or 13 = flame not proven, 12 = weak flame (furnace still runs).
  5. The blower should come on at high heat speed roughly 15 to 20 s after the burners light; if 22 or 33 shows, check airflow, limits, rollouts and overfiring.
  6. Remove the W2 call and confirm the inducer and blower switch to low; then end the call and confirm post-purge and the blower off delay.
  7. To reset a lockout cut main power 30 seconds, or remove the heat call for more than 2 but less than 20 seconds (soft lockout).

Applies to: (-)96VA040-115 (R96V / U96V) and (-)(-)96MDV040-115 two-stage variable-speed communicating furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rheem (-)96V / (-)(-)96MDV Installation Instructions 92-24161-124-08, Fig. 64 2-stage furnace troubleshooting chart p.124-125. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.