Rheem · Furnace troubleshooting
Heat call troubleshooting walk-through (two-stage communicating IFC)
What is going on
Order of checks from the factory diagnostic chart when a heat call does not end in high-fire heat.
Likely causes
- No W1/W2 or communicated call
- Dipswitch or test-mode setting
- Inducer not starting or pressure switches not closing
- No spark or no flame proof
- Blower not starting on heat speed
Check in this order
- Communicating systems pull E1/E2 off the thermostat and jumper W1-R and W2-R to force high heat. Legacy: confirm 24 VAC on W1 and W2 at the IFC.
- Displays should light and show a steady H (h = low heat only). Flashing H means check the dipswitches.
- Inducer should pre-purge about 30 seconds at high speed. If it runs 60 seconds then stops for five minutes with 45, 46 or 57 showing, work the pressure switch fault.
- Watch for spark; the gas valve is powered about 7 seconds per trial, four trials before a one-hour lockout. 11 or 13 = flame not proven, 12 = weak flame (furnace still runs).
- The blower should come on at high heat speed roughly 15 to 20 s after the burners light; if 22 or 33 shows, check airflow, limits, rollouts and overfiring.
- Remove the W2 call and confirm the inducer and blower switch to low; then end the call and confirm post-purge and the blower off delay.
- To reset a lockout cut main power 30 seconds, or remove the heat call for more than 2 but less than 20 seconds (soft lockout).
Applies to: (-)96VA040-115 (R96V / U96V) and (-)(-)96MDV040-115 two-stage variable-speed communicating furnaces
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rheem (-)96V / (-)(-)96MDV Installation Instructions 92-24161-124-08, Fig. 64 2-stage furnace troubleshooting chart p.124-125. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.