Trane · Furnace troubleshooting

General venting requirements

UH1 / DH1

What is going on

Furnaces are induced draft, Category IV, positive vent pressure. Vent must be gas tight and water tight.

Check in this order

  1. Vent the furnace to the outdoors. Do not connect it to any vent serving another appliance.
  2. Ship setting is direct vent with sealed combustion. Combustion air must come through the inlet pipe from outside air for direct vent.
  3. For nondirect vent (single pipe), combustion air may come from the surrounding area if combustion air requirements are met.
  4. Use 2 in, 2-1/2 in or 3 in plastic pipe (Table 10). Where venting goes through a masonry chimney that carries another gas appliance's flue products, or where local code requires it, use 3 in Type 29-4C stainless steel instead.
  5. Keep the snow clear from the vent area (building owner or maintenance provider responsibility).
  6. Make sure the vent system drains condensate and does not deteriorate.

Applies to: All UH1 and DH1 furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane AUH1B080A9421B installer's manual, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.