Rheem · Furnace troubleshooting

Gas valve does not shut off when heat call ends

What is going on

If the burners stay lit after the thermostat is turned off, treat it as an emergency until the gas is shut off. Most of the time, in my experience, the thermostat or its wiring is still calling for heat, or the thermostat is sitting on FAN and someone thinks that is the problem. A gas valve that is stuck open is rare but it is the dangerous one. Close the manual gas valve to the appliance first. Then figure out why it is still energized. This applies to Rheem (-)GRC/(-)GTC and 90RJ/90TJ 90 Plus condensing furnaces.

Likely causes

  • W still energized from the thermostat or wiring, or thermostat in FAN
  • IFC still powering the gas valve
  • Gas valve stuck open
  • Shorted thermostat wires at a splice or the subbase

Check in this order

  1. Warning: if gas will not shut off, close the manual gas valve to the appliance before turning off the electrical supply, risk of explosion or fire
  2. Set the thermostat to OFF and confirm W to C is 0 V at the IFC, make sure the thermostat is not in FAN
  3. If W shows voltage with the stat off, check the thermostat and wiring for a short
  4. Check for voltage at the gas valve present with W off means check the IFC, absent means replace the gas valve
  5. After shutdown confirm the inducer stops after the 10-second post-purge and the blower stops within 3 minutes max, if not, check the IFC
  6. Gas valve replacement and gas leak testing are for a licensed technician

Applies to: Rheem (-)GRC/(-)GTC and 90RJ/90TJ 90 Plus condensing gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rheem (-)GRC/(-)GTC Installation Instructions 92-24161-88-00, Figure 56 IFC Troubleshooting Guide, p.54 (printed); Rheem 90RJ/90TJ Installation Instructions 92-24161-32-08, Figure 53, p.54. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.