Trane · Furnace troubleshooting

Gas supply pressure testing

UH1 / DH1

What is going on

Gas line pressure testing and the furnace valve: protect the valve from test pressure above 1/2 psig. Higher than that damages the gas valve.

Likely causes

  • Furnace left connected during a test above 1/2 psig
  • Individual manual shut-off valve left open on a low pressure test
  • Test pressure not matched to isolation method

Check in this order

  1. For tests above 1/2 psig (3.5 kPa), disconnect the furnace and its shut-off valve from the gas supply.
  2. For tests at or below 1/2 psig (3.5 kPa), close the furnace's individual manual shut-off valve to isolate it.
  3. Cap the open line before pressurizing.
  4. After the test, reconnect and leak check all joints before opening the valve.

Applies to: Gas line pressure tests

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane 18-CD29D1-11 installer's guide, p. 35. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.