Furnace short cycles or does not hold setpoint
What is going on
Rheem 802PA furnaces and matching 80MDP models: heat cycles end early or the room temperature drifts away from the setpoint. Applies to (-)802PA050314MSA, (-)802PA075417MSA, (-)802PA100521MSA, (-)802PA125524MSA, (-)802PA150524MSA.
Likely causes
- Thermostat in a bad spot, so it satisfies before the house does
- Heat anticipator set wrong
- Limit opening and closing on low airflow, which shows as code 22
- Furnace oversized for the load
Check in this order
- Check thermostat location, because registers, sunlight, and pipes or wires in the wall behind it all fool it
- Check the heat anticipator setting; an isolation relay may be needed on some thermostats
- See whether a limit is cycling (code 22), and check the filter, ducts and blower speed because restricted air heats the exchanger fast
- Measure temperature rise and compare it to the rating plate range
- Verify furnace size against the load, since an oversized unit short cycles even when everything else is right
Applies to: (-)802PA050314MSA, (-)802PA075417MSA, (-)802PA100521MSA, (-)802PA125524MSA, (-)802PA150524MSA and matching (-)(-)80MDP models
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rheem (-)802P/(-)(-)80MDP Installation Instructions 92-24161-146-02, Diagnostics Flowchart (Figure 33), p.51. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.