Rheem · Furnace troubleshooting
Furnace no heat - sequence troubleshooting
What is going on
Step through the normal heat sequence: pressure switch check, 30-second prepurge, 8-second ignition trial on low fire, blower on about 20 seconds after ignition, staging, 10-second post-purge.
Likely causes
- No 24V on W
- Inducer or pressure switch problem
- No spark
- No gas / low gas pressure
- Weak flame sense
- Limit or roll-out open
- Blower not starting
Check in this order
- Set fan to AUTO and call for low heat. If a fault code shows, follow that code.
- Confirm 24V on W at the IFC; if none, check thermostat, batteries and wiring.
- Inducer should run 30-second prepurge; if it runs 60 seconds then stops for 5 minutes, the pressure switch did not close - check hoses, vent, inducer.
- Check spark during the trial; check igniter, wires and placement.
- If burners light but drop out, clean flame sensor, check polarity and ground, check gas pressure.
- Blower should start about 20 seconds after ignition; if not, check HEAT-NEUTRAL voltage, wiring, capacitor and motor.
- For high heat, check 24VAC on W2 and that the high gas valve is energized.
- Most failures are not the IFC - check wiring and ground before replacing it.
Applies to: (-)802PA050314MSA, (-)802PA075417MSA, (-)802PA100521MSA, (-)802PA125524MSA, (-)802PA150524MSA and matching (-)(-)80MDP models
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rheem (-)802P/(-)(-)80MDP Installation Instructions 92-24161-146-02, Sequence of Operation / Diagnostics Flowchart (Figure 33), p.39, 51. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.