Furnace in attic or crawl space (horizontal)

UH1/DH1

What is going on

Placement rules for a horizontal furnace in an attic or crawl space. Mostly about clearances, access and keeping the unit dry and supported.

Likely causes

  • Horizontal furnace going into an attic, where service access and framing contact matter
  • Horizontal furnace in a crawl space where moisture is a concern
  • Suspended installs hung from joists or rafters
  • Replacement jobs where the old platform is too small or in the wrong place

Check in this order

  1. In an attic, place the furnace on the left side (as viewed from front in vertical position)
  2. Build a service platform large enough for clearances on all sides and front service access, because a tech has to reach the blower and burners
  3. Make sure only line contact occurs between the furnace casing edges and joists, studs or framing
  4. In a crawl space, set the furnace on a pad or noncombustible material to keep it dry
  5. If suspended, use 3/8 in all-thread rods with angle iron at both ends and the midpoint
  6. Make the angle iron at least 32 in long so panels can be reached
  7. Check the finished install for clearance to combustibles per the rating plate

Applies to: Horizontal UH1/DH1 furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane installer's guide 18-CD29D1-11, p. 7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.