Rheem · Furnace troubleshooting
Five-minute lockout (low pressure switch fails to close)
What is going on
A five-minute soft lockout starts if the low pressure switch does not close within 60 seconds of continuous inducer operation at the start of a heat cycle. The display shows the matching fault. The lockout clears automatically after five minutes, so the furnace may seem to fix itself and then do it again. Be careful when you inspect the vent, because flue gases can contain carbon monoxide. Power off before touching hoses or wiring, and call a licensed technician if the vent or combustion looks wrong.
Likely causes
- Low pressure switch not closing during the proving period
- Blocked or restricted venting, including a clogged intake or terminal
- Loose or faulty wiring
- Faulty pressure switch or hoses
- Condensate backing up into the pressure switch hose
Check in this order
- Check the vent system for blockage and proper termination
- Check the pressure switch hoses for blockage, splits, or disconnection
- Look for water in the hose or switch, which means a drain problem
- Check the pressure switch and wiring
- Wait five minutes for automatic reset, or clear the original fault and cycle power
- Watch the next heat cycle and confirm the switch closes within the proving time
- If it keeps locking out, have a licensed tech check vent and inducer
Applies to: R96V furnace
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rheem 96V series installation instructions, p. 118. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.