Rheem · Furnace troubleshooting
Final review after a horizontal conversion
What is going on
Last pass on a Rheem 96V/96MDV horizontal conversion, before you leave the job. Tick every item on the printed checklist. Skip one and you're back for a leak or a vent problem.
Likely causes
- Not a fault call. Final review list for horizontal conversions.
Check in this order
- Verify all hoses are secure and fully seated.
- Confirm all hoses are free of kinks.
- Confirm all hoses and other drain parts slope in the direction of water flow.
- Make sure both worm drives on the flue transition hose clamps sit on the top of the coupling.
- Tighten all clamps and couplings.
- Confirm all drain ports are plugged.
- Confirm the unit has forward pitch.
- Install heat tape if required.
Applies to: Horizontal conversions
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rheem 96V installation manual, p. 38. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.