Trane · Furnace troubleshooting
Filter placement for upflow furnace in horizontal configuration
What is going on
Before you lay an upflow Trane furnace on its side, think about the filter first. The manual says a filter must never sit inside or outside the cabinet directly above the blower assembly in a horizontal setup. Confirm where the return and filter will end up before the unit is set.
Likely causes
- Filter placed directly above the blower in a horizontal install
- No remote filter or upstream filter provision in the ductwork
- Wrong conversion kit for the cabinet width
Check in this order
- Do not place the filter directly above the blower, inside or outside the cabinet.
- Use a remote filter grille, or install the filter in the ductwork upstream of the furnace.
- For conversion, use filter kit BAYFLTR203 (17.5 in cabinet), BAYFLTR204 (21 in) or BAYFLTR205 (24.5 in). These include the filters and brackets needed for horizontal filters.
- Match the kit to your cabinet width before ordering.
- After installation, confirm the filter is seated and no air bypasses it.
Applies to: Upflow furnace in horizontal configuration
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Trane AUH1B080A9421B installer's manual, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.