Allied · Furnace troubleshooting

Exhaust and air intake pipe check during startup

A95/A93/95G1/92G1UH

What is going on

Use this when the furnace shuts off at the pressure switch, or when a flame rollout switch opens. Both often trace back to the venting. Before opening any panel or resetting anything, turn off power at the disconnect and make sure the furnace has cooled. An open rollout switch means flame came out of the burner box at some point, which is a real safety event, so find the cause before you put the furnace back in service.

Likely causes

  • Obstructed exhaust pipe
  • Loose exhaust or intake connection
  • Blocked termination from snow, ice, leaves or a nest
  • Opened flame rollout switch caused by obstructed pipe
  • Cracked or leaking pipe section

Check in this order

  1. Turn off power and let the furnace cool before opening any panel.
  2. Check exhaust and air intake connections for tightness.
  3. Check the pipe for blockage along its full length.
  4. Confirm the pressure switch is closed when the inducer runs; an obstructed exhaust makes the unit shut off at the switch. Use a meter across the switch to confirm.
  5. Check the termination for blockages.
  6. Reset the manual flame rollout switches on the burner box only after the cause is found and corrected. Do not defeat any safety.
  7. If rollout trips again, call a licensed technician.

Applies to: Exhaust and intake venting

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Allied 92G1UH installation instructions manual, p. 46. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.