Rheem · Furnace troubleshooting

Example: checking orifice size at high altitude (natural gas)

96V96MDV

What is going on

Worked example of orifice sizing for natural gas at altitude, using a 900 BTU/ft3 regional gas. These numbers are for the example only. Do not reuse them on another site, use the local heating value and the manual tables.

Likely causes

  • Not a fault call. Reference example showing how altitude derating changes the orifice.

Check in this order

  1. Calculate Q = I / H: 14000 / 900 = 15.56 ft3 per hour (I = sea level input per burner, H = heating value).
  2. Find the sea level orifice for 3.5 in. w.c. in NFGC Table E.1.1(a): #49.
  3. Find the orifice at 5000 ft using NFGC Table E.1.1(d) with 4% derate per thousand ft: #51.
  4. Find the orifice at 8000 ft using the same method: #52.
  5. On a real job, get the heating value from the gas utility, not from this example.
  6. Orifice changes and gas input adjustment are for a licensed gas technician.

Applies to: Natural gas orifice sizing above 2,000 ft

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: 96V series installation instructions, p. 80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.