Allied · Furnace troubleshooting

Electrical checks on the furnace

A95/A93/95G1/92G1UH

What is going on

A basic electrical checkout on the Allied furnace is quick and catches a lot. You are looking for loose connections, low supply voltage and a blower motor that pulls more current than its nameplate says. Do the wiring check with the power off, then the live readings with the furnace running.

Likely causes

  • Loose or burnt wire connection
  • Supply voltage outside 120 VAC plus or minus 10%
  • Blower motor drawing more amps than its nameplate, from a failing motor or restricted airflow

Check in this order

  1. Turn off power and check all wiring for loose connections.
  2. Restore power and run the furnace.
  3. Check supply voltage at the furnace. Correct voltage is 120 VAC ±10%.
  4. With the blower access panel in place, check blower motor amp draw with a clamp meter and compare it with the motor nameplate.
  5. If a reading is off, find the cause before leaving, and call a licensed technician for anything inside the line voltage wiring you are not comfortable with.

Applies to: Furnace electrical checkout

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Allied 92G1UH installation instructions manual, p. 46. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.