Rheem · Furnace troubleshooting
ECM blower will not run - power and communication checks (code 68)
What is going on
The communicating blower motor does not start on a heat, cool or fan call and the control shows 68.
Likely causes
- No 115-120 VAC at the motor line connector
- Pins not seated in the 5-pin or control connector
- Control cable between P5 and the motor damaged
- Failed motor module
Check in this order
- Unplug the 5-pin line voltage connector at the motor. With the door switch closed, check for 115-120 VAC between pins 4 and 5; line voltage should be there whenever the furnace is powered. No voltage: fix the wiring. Make sure every pin is fully seated, then plug it back in.
- Unplug the motor control connector from P5 on the control and put 24 VAC on pins 3 and 4 of the motor side. With the door switch closed the motor should run at about 75%.
- Motor runs in that test the problem is the control or the control cable, not the motor.
- Motor does not run check the control cable end to end and pin seating; if the wiring is good, replace the motor.
Applies to: (-)96VA040-115 (R96V / U96V) and (-)(-)96MDV040-115 two-stage variable-speed communicating furnaces
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rheem (-)96V / (-)(-)96MDV Installation Instructions 92-24161-124-08, Diagnosing blower motor issues p.122, Fig. 62. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.