Rheem · Furnace troubleshooting
ECM blower does not start on heat
What is going on
RGPE/RGLE: blower should start on high heat speed 15-20 seconds after burners light.
Likely causes
- Loose IFC-ECM connections
- No 24 V to ECM control
- PFC choke
- No 115 VAC to motor
- Dipswitch settings
Check in this order
- Check all connections between IFC and ECM motor.
- Check 24 V at the ECM 4-pin control connector, pins 1 and 4.
- Check dipswitch settings.
- Check the PFC choke and its wiring.
- Check 115 VAC line voltage to the motor.
- Read the fault code on the displays.
Applies to: Rheem/Ruud (-)GPE upflow/horizontal and (-)GLE downflow 2-stage 80+ communicating gas furnaces
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rheem RGPE/RGLE Installation Instructions 92-24161-77-02 (ManualsLib 1287511), Figure 45 Troubleshooting Chart, p.63 (PDF p.67). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.