ECM blower does not start on heat

What is going on

RGPE/RGLE: ECM blower not starting on heat. It should come on at high heat speed 15-20 seconds after the burners light. Rheem/Ruud (-)GPE and (-)GLE 2-stage 80+ communicating furnaces. Usually a connection or a missing control voltage.

Likely causes

  • Loose connections between the IFC and the ECM motor
  • No 24 V to the ECM control
  • PFC choke or its wiring
  • No 115 VAC to the motor
  • Dipswitch settings wrong

Check in this order

  1. Read the fault code on the displays first.
  2. Check all connections between the IFC and the ECM motor.
  3. Check 24 V at the ECM 4-pin control connector, pins 1 and 4.
  4. Check the dipswitch settings.
  5. Check the PFC choke and its wiring.
  6. Check 115 VAC line voltage to the motor, with the power handled safely.

Applies to: Rheem/Ruud (-)GPE upflow/horizontal and (-)GLE downflow 2-stage 80+ communicating gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rheem RGPE/RGLE Installation Instructions 92-24161-77-02 (ManualsLib 1287511), Figure 45 Troubleshooting Chart, p.63 (PDF p.67). Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.