Trane · Furnace troubleshooting

Downward venting

AUH1BUH1DH1

What is going on

Downward venting is when the vent has to go down before it goes out, usually through a basement wall or floor. It works, but it is limited in length, and because water naturally runs down the pipe you need a condensate trap on the vent so it does not run back into the furnace. Think of it like a kitchen sink trap. Slopes and supports are what keep the system working long term.

Likely causes

  • Downward run longer than allowed
  • No condensate trap on the vent, so water runs to the furnace
  • Horizontal pipes without slope holding water
  • Trap drain not connected to a proper drain
  • Termination too low or too high above the roof

Check in this order

  1. Limit downward vent length to a maximum of 15 equivalent feet.
  2. Install a condensate trap of at least 6 in height on the vent pipe.
  3. Slope all horizontal pipes at 1/4 in per foot and support them at no more than 3 ft intervals.
  4. Connect the vent and inlet condensate trap to a condensate drain pump, an open or vented drain, or the outlet hose of the furnace condensate trap.
  5. Keep 12 in minimum clearance above the highest expected snow level, not exceeding 24 in above the roof.
  6. After startup, check that the trap holds water and drains freely.

Applies to: Vertical/downward venting from a 40 in upflow or downflow furnace

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Trane installer's guide, p. 23. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.