Trane · Furnace troubleshooting
Downward venting
What is going on
Downward venting is when the vent has to go down before it goes out, usually through a basement wall or floor. It works, but it is limited in length, and because water naturally runs down the pipe you need a condensate trap on the vent so it does not run back into the furnace. Think of it like a kitchen sink trap. Slopes and supports are what keep the system working long term.
Likely causes
- Downward run longer than allowed
- No condensate trap on the vent, so water runs to the furnace
- Horizontal pipes without slope holding water
- Trap drain not connected to a proper drain
- Termination too low or too high above the roof
Check in this order
- Limit downward vent length to a maximum of 15 equivalent feet.
- Install a condensate trap of at least 6 in height on the vent pipe.
- Slope all horizontal pipes at 1/4 in per foot and support them at no more than 3 ft intervals.
- Connect the vent and inlet condensate trap to a condensate drain pump, an open or vented drain, or the outlet hose of the furnace condensate trap.
- Keep 12 in minimum clearance above the highest expected snow level, not exceeding 24 in above the roof.
- After startup, check that the trap holds water and drains freely.
Applies to: Vertical/downward venting from a 40 in upflow or downflow furnace
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Trane installer's guide, p. 23. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.