Allied · Furnace troubleshooting

Direct vent termination layout (roof and sidewall)

A95/A93/95G1/92G1UH

What is going on

Intake and exhaust must share the same pressure zone, and the two pipes should be as close together as possible at the termination.

Check in this order

  1. Make sure intake and exhaust both exit through the roof or both through the side wall. Do not split them.
  2. Keep intake and exhaust on the same side of the structure.
  3. Keep the separation at the terminations to 3 in. (76 mm) maximum on roof terminations and 6 in. (152 mm) maximum on sidewall terminations.
  4. On a roof termination, turn the intake straight down using two 90 degree elbows.
  5. Run the exhaust straight out or straight up.
  6. Fit an exhaust reducer where the pipe exits the structure if needed to increase exhaust velocity away from the intake (see table 6).
  7. Route the piping to avoid recirculating exhaust back into the intake.

Applies to: Direct vent terminations

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Allied 92G1UH installation instructions manual, p. 30. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.