Rheem · Furnace troubleshooting

Direct vent: alternate horizontal termination (Options 4 and 5)

96V96MDV

What is going on

Alternate horizontal termination with the intake and exhaust spaced as shown. Option A requires a trap in the combustion air pipe. Option B does not. Wall penetrations and terminations must use 2 in pipe, and a 3 in vent may be necessary to step down to 2 in.

Check in this order

  1. Keep the termination at 12 in above grade or expected snow level (U.S.).
  2. Keep intake and exhaust spacing as shown 3 in minimum and 5 in maximum at the termination.
  3. Keep the intake about 12 in from the wall and the exhaust about 6 in minimum from the wall, per the figure.
  4. For Option A, install a trap in the combustion air pipe (RXGY-D05 for 2 in or RXGY-D06 for 3 in).
  5. For Option B, no trap is required.
  6. Limit 2 in pipe inside the wall to 18 in maximum when using 3 in vent.
  7. Install the wind deflector vane in a 2 in PVC coupling in the vertical position using PVC solvent.
  8. Make the intake and exhaust terminations in the same pressure zone.
  9. Do not use screens or tees at the termination.
  10. Insulate external piping as required for local climate.

Applies to: Direct vent alternate horizontal termination (Options 4 and 5)

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rheem 96V installation instructions, p. 61. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.