Trane · Furnace troubleshooting
Condensate drain for vertical upflow and downflow installations
What is going on
Upflow and downflow units use different drain tubing and trap routing, and the drain should have a drain pan under it.
Check in this order
- Install a drain pan under the furnace to prevent leak damage.
- Upflow find the drain tubing for left and right side drainage in the blower compartment. Run it from the trap to the side of the unit, and trim excess to avoid kinks.
- Upflow use the 2 in to 3 in reducing coupling marked TOP, with the TOP mark on the top side of the pipe and the straight side on the bottom.
- Downflow seal the fitting to the trap with RTV silicone so the trap can be removed for cleaning.
- Downflow left side use a 1/2 in slip PVC fitting.
- Downflow right side remove the drain lines, rotate the trap 180 degrees, and reconnect. Use a 1/2 in 90 degree CPVC street elbow sealed with RTV, 1/2 in CPVC to an elbow, then 1/2 in CPVC out through the right side knockout.
Applies to: Upflow and downflow vertical installations
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Trane installer's guide, p. 26. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.