Rheem · Furnace troubleshooting

Communicating system not found / no communication

What is going on

On a Rheem/Ruud RGPE or RGLE communicating furnace, the thermostat should show SEARCHING, then FURNACE FOUND and AIR CONDITIONER or HEAT PUMP FOUND within 30 minutes. When it never finds the equipment, nine times out of ten it is a wiring problem and not a bad board. The usual culprit is a switch left in the wrong position on the furnace control, or a wire run that is too long, too thin or full of splices. I have also seen old wire ends corroded enough to kill the signal. Look at the cheap stuff first.

Likely causes

  • SW4 TERM/BIAS switches not all ON
  • Wire too long or too small
  • Old or corroded wire ends
  • Wiring not direct, with splices or a daisy chain through other devices

Check in this order

  1. Make sure all three SW4 dipswitches are ON
  2. Max wire length thermostat to furnace 100 ft, furnace to condenser 125 ft, 18 AWG minimum
  3. Wires 1 and 2 should be a twisted pair (green on 1, yellow on 2 recommended)
  4. Trim and re-strip existing wires to expose fresh copper
  5. Run dedicated 1, 2, R, C wires directly furnace to thermostat and furnace to condenser
  6. With power off, check each conductor for continuity end to end, and for a short between wires
  7. Power the system back up and wait for the thermostat to complete its search

Applies to: Rheem/Ruud (-)GPE upflow/horizontal and (-)GLE downflow 2-stage 80+ communicating gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rheem RGPE/RGLE Installation Instructions 92-24161-77-02 (ManualsLib 1287511), Communicating systems - wiring and startup, p.49 (PDF p.53). Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.