Trane · Furnace troubleshooting
Combustion and input check
What is going on
Combustion and input check means finding out how much gas the furnace is actually burning. You do it by timing the gas meter with only the furnace running, then converting to input and comparing to the nameplate. It sounds fiddly but it is simple arithmetic, and it tells you quickly if the unit is over or underfired. Overfiring shortens heat exchanger life and can create unsafe combustion.
Likely causes
- Gas input above the nameplate rating
- Other gas appliances left on during the test
- Dial size misread or wrong conversion
- Wrong orifices or high manifold pressure
- Utility heating value assumed instead of read from the bill
Check in this order
- Make sure all other gas appliances are off, including pilots.
- With the furnace running, clock the gas meter for one revolution and note the dial size.
- Find the clocked seconds in the flow table and read the cfh on the same row.
- Adjust the reading for dial size a 1 cu ft dial divide by 2; a 1/2 cu ft dial divide by 4; a 5 cu ft dial multiply by 10 and divide by 4.
- Multiply the result by the gas heating value from the utility and compare to the nameplate. It must not exceed the nameplate rating.
- If input is too high, check manifold pressure and orifice size. Gas adjustments are for a licensed technician.
- Relight other appliances when done.
Applies to: All UH1 and DH1 furnaces
More furnace guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Trane 18-CD29D1-11 installer's guide, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.